P6010 & p8010 indicators – serial communications, Bit parameters – Pyromation Series 610 1_16 DIN User Manual

Page 119

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

P6010 & P8010 Indicators – Serial Communications Parameters

The Modbus parameter addresses, and the possible ASCII message types and parameters
indents for the P6010 & P8010 are detailed below.

RO indicates a parameter is read only,

WO indicates a parameter is write only and R/W indicates it can read from or written to.
Communications writes will not implemented if the Communications Write Parameter is
disabled. Refer to the Modbus and ASCII Communications sections of this manual for details
of the protocols used.

Bit Parameters

Bit parameters are not applicable to the ASCII protocol.

Table 29. P6010 & P8010 Communications - Bit Parameters

Parameter

Modbus

Parameter No.

Notes

Alarm 2 Status
Alarm 3 Status

3

RO

1 = Active, 0 = Inactive

RO

1 = Alarm 1 Latched, 0 = Not Latched*

RO

1 = PV Under-range, 0 = PV within range

PV Over Range

6

RO

7

RO

1 = Sensor Break Active, 0 = Sensor Break Inactive

8

WO

Writing any value resets all latched alarm relays.
Note: Outputs will only reset if their alarm condition
is no longer present.

Reset Maximum PV

9

Writing any value resets the stored maximum displayed
PV value

Reset Minimum PV

10

WO

Alarm 1 Status

1

RO

1 = Active, 0 = Inactive

2

RO

1 = Active, 0 = Inactive

Alarm 1 Latched

4

PV Under Range

5

1 = PV Over-range, 0 = PV within range

Sensor Break
Latched Alarm
Reset

WO

Writing any value resets the stored minimum displayed
PV value

Reset Elapsed
Time

11

WO

Writing any value resets the stored alarm 1 active time
value

Alarm 5 Status

12

RO

1 = Active, 0 = Inactive

Alarm 5 Status

13

RO

1 = Active, 0 = Inactive

Alarm 2 Latched

14

RO

1 = Alarm 2 Latched, 0 = Not Latched*

Alarm 3 Latched

15

RO

1 = Alarm 3 Latched, 0 = Not Latched*

Alarm 4 Latched

17

RO

1 = Alarm 5 Latched, 0 = Not Latched*

To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section

*Note:

Alarm Latched status requests always returns 0 if that alarm is not configured to be
latching.

16

RO

1 = Alarm 4 Latched, 0 = Not Latched*

Alarm 5 Latched


Page 114

P6010 & P8010 Model Group

59305, Issue 6 – March 2006