Panel cut-outs, Panel-mounting, Figure 2. panel cut-out sizes – Pyromation Series 610 1_16 DIN User Manual

Page 17

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

Panel Cut-outs

The mounting panel must be rigid and may be up to 6.0mm (0.25 inches) thick. The cut-outs
required for the instruments are shown below.

1

/

16

DIN

45mm

+0.5 –0.0

1

/

8

DIN

92mm

+0.5 –0.0

(45mm for

indicator)

1

/

4

DIN

92mm

+0.5 –0.0

92mm

+0.5 –0.0

45mm +0.5 –0.0

(92mm for indicator)

45mm

+0.5 –0.0

Figure 2. Panel cut-out sizes

Panel-Mounting

CAUTION:

Ensure the inside of the panel is with the instruments operating temperature and
that there is adequate air flow to prevent overheating.

Hold firmly in position

(apply pressure to bezel only)

Mounting Panel

Instrument Housing

Ratchets

Gasket

Slide mounting clamp over the

instrument housing, towards rear face of

mounting panel, until the tongues

engage in ratchets and instrument is

clamped in position

.

Figure 3. Panel-Mounting the instrument

CAUTION:

Do not remove the panel gasket, as this may result in inadequate clamping and
sealing of the instrument to the panel.


Page 12

Installation

59305, Issue 6 – March 2006

Advertising