Manual Control Mode

To allow manual control to be selected in Operator Mode,

@ !C

must be enabled in Set Up

Mode. Manual Mode can be selected using the front keys or by use of a digital input if one
has been fitted and configured for this function.

Selecting/deselecting Manual Control Mode

Press the key to toggle between Automatic and Manual control.

The indicator flashes continually in Manual Mode

Press or to adjust the output power to the required value.

CAUTION:

The Manual Mode power level can be adjusted from 0 to 100% (-100 to +100% for
dual output). It is not restricted by the Output Power Limit parameter

)1'

.

Note:

Disabling

@ !C

in Set Up Mode whilst manual control mode is active will lock the controller

into manual mode. Pressing the Auto/Man key will no longer cause a return to automatic
control. To exit from Manual Mode,

@ !C

must temporarily be re-enabled.