P6170, p8170 & p4170 – setup mode, Entry into the setup mode, Scrolling through parameters & values – Pyromation Series 610 1_16 DIN User Manual

Page 77: Changing parameter values, Adjusting the valve parameters

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

P6170, P8170 & P4170 – Setup Mode

This mode is normally selected only after Configuration Mode has been completed, and is
used when a change to the process set up is required. It can affect the range of adjustments
available in Operator Mode. Some Setup Mode parameters can be copied into Operator
Mode by the PC Configurator software. This is called Extended Operator Mode. These
parameters appear after the normal Operator Mode screen sequence has been completed.

Note:

Entry into Setup Mode is security-protected by the Setup Mode lock code.

Entry into the Setup Mode

Hold down and press to enter the Select Mode

Press or to navigate to the Setup Mode option, then press to enter
Setup Mode.

Scrolling through Parameters & Values

Press to scroll through the parameters (refer to the table below) and their values.

Changing Parameter Values

Press to select the required parameter, then press or to set the value as
required.

Once the displayed value is changed, the effect is immediate. No confirmation of the
change is required.

Note:

If there is no key activity for two minutes the instrument returns to the operator mode.

Adjusting the Valve Parameters

Before Valve Position Indication can be used, the user must first adjust the Set Valve
Opened Position and Set Valve Closed Position parameters. These define the input value
that will be measured by the Auxiliary Input when the valve is at its physical end stops. They
must be set correctly even if the valve will not be driven to its end stops in the application.
The user may optionally set the Valve Open Limit and Valve Close Limit. These are upper
and lower valve position clamps, which the controller will not attempt to drive the valve past.

Note:

Valve Position Indication is only possible if an Auxiliary Input option module is fitted, and
has been configured for this function.


Page 72

P6170, P8170 & P4170 Model Group

59305, Issue 6 – March 2006

Advertising
This manual is related to the following products: