Sensor Placement (Thermocouple or RTD)

If the temperature probe is to be subjected to corrosive or abrasive conditions, it must be
protected by an appropriate thermowell. The probe must be positioned to reflect true process
temperature:

1. In a liquid media - the most agitated area

2. In air - the best circulated area

CAUTION:

The placement of probes into pipe work some distance from the heating vessel
leads to transport delay, which results in poor control.

For a two wire RTD a wire link should be used in place of the third wire. Two wire RTDs must
only be used with lead lengths less than 3 metres. Use of three wire RTDs is strongly
recommended.

Thermocouple Wire Identification Chart

The different thermocouple types are identified by their wires colour, and where possible, the
outer insulation as well. There are several standards in use throughout the world.

The table below shows the wire and sheath colours used for most
common thermocouple types. The format used in this table is:

+

Wire

-

Wire

Sheath

Table 2. Thermocouple Extension Wire Colours

Type International

IEC584-3

USA ANSI

MC 96.1

British

BS1843

French

NFC 42-324

German

DIN 43710

+*

Black

White

Yellow

Yellow

Red

J

-

White

Black

Red

Black

Blue

Black

Black

Black

Blue

Blue

+

Brown

Blue

White

Yellow

Red

T

-

White

Brown

Red

Blue

Blue

Blue

Blue

Blue

Brown

Brown

+

Green

Yellow

Brown

Yellow

Red

K

-*

White

Green

Red

Yellow

Blue

Red

Purple

Yellow

Green

Green

+

Pink

Orange

Orange

N

-

White

Pink

Red

Orange

Blue

Orange

+

Grey

Grey

Red

B

-

White

Grey

Red

Grey

Grey

Grey

+

Orange

Black

White

Yellow

Red

R & S

-

White

Orange

Red

Green

Blue

Green

Green

Green

White

White

+

White

C (W5)

-

Red

White

Note:

* = Wire is magnetic


Page 22

Connections

59305, Issue 6 – March 2006