Easicool™ precision air conditioning – Airedale EasiCool 6kW 64kW User Manual

Page 23

Advertising
background image

EasiCool™

Precision Air Conditioning

Controls

Temperature Control

A temperature sensor is mounted in the return air with an option for a humidity sensor on full function units.

The temperature sensor is a NTC type thermistor accurate up to +/- 0.25°C and the humidity sensor accurate to +/-
3% RH at 25°C at the sensor.

The microprocessor senses the return air conditions and maintains the return air temperature and humidity
conditions by controlling cooling, heating, humidification and dehumidification outputs accordingly.

Monitoring

The microprocessor monitors and displays the following values:

• Return Air Temperature
• Return Air Humidity (Optional on Full Function units)
• Condensing Pressure (Optional on DX units only)
• Coil Temperature Sensor (Indoor)

The maintenance of key components such as compressors and air filters can be monitored via a service indicator
which visually demonstrates the status relative to the component service intervals.

Alarm Log

The controller logs and allows viewing of the last 100 conditions recorded in descending chronological order
through the keypad display.

The standard display keypad visually displays operating alarms, however, as an optional extra, a display keypad
with audible alarms is available.

Modbus / Carel BMS Connection

The Airedale controllers shall be able to communicate directly using the Modbus® protocol.

The Modbus® card shall be a small PCB (60mm x 30mm), which can be plugged into the controller to provide it
with the following protocol support

Modbus® - JBus slave
RTU mode (Remote Terminal Unit) with 8 bit encoding and error handling using 16 bit CRC
Communication standard connection options of RS485 (multipoint) or RS232 (point-point)
Maximum Baud Rate of 19200

The data communication shall be asynchronous serial, 8 data bits, 2 stop bits and no parity (in total 11 bits/datum).

The data/parameters from the controller shall be represented within Modbus® registers, each register containing
information pertaining to temperatures, pressures, setpoint, status, etc and is available to the site integration
company in a spreadsheet format

23

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Introduction

Advertising