Easicool™ precision air conditioning, Te ch nic al x-t yp e df, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual

Page 57: Performance data standard condenser, Operating limits

Advertising
background image

EasiCool™

Precision Air Conditioning

57

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

DF

Cooling Capacity (1)

Ambient

Air On

25°C

30°C

35°C

40°C

(DB°C/%RH)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

DF28X-EZRE CR50

22/50

25.0

24.3

25.0

24.3

25.0

24.3

23.8

23.4

24/45

26.1

26.1

26.1

26.1

26.1

26.1

24.9

24.9

26/40

27.4

27.4

27.4

27.4

27.3

27.3

26.2

26.2

DF31X-EZRE CR50

22/50

28.4

28.2

28.4

28.2

28.2

28.1

26.8

26.8

24/45

29.7

29.7

29.7

29.7

29.4

29.4

28.0

28.0

26/40

31.2

31.2

31.2

31.2

30.8

30.8

29.5

29.0

DF35X-EZRE CR50

22/50

32.9

32.5

32.9

32.5

32.3

31.9

30.7

30.5

24/45

34.5

34.5

34.5

34.5

33.7

33.7

32.2

32.2

26/40

36.3

36.3

36.3

36.3

35.5

34.9

34.2

32.5

DF40X-EZRE CR65

22/50

36.7

36.6

36.7

36.6

36.6

36.5

34.7

34.7

24/45

38.5

38.5

38.5

38.5

38.2

38.2

36.4

36.4

26/40

40.4

40.4

40.4

40.4

40.1

40.0

38.6

37.4

DF45X-EZRE CR80

22/50

41.4

39.2

41.4

39.2

41.4

39.2

39.5

37.9

24/45

43.2

42.9

43.2

42.9

43.2

42.9

41.1

41.1

26/40

45.1

45.1

45.1

45.1

45.0

45.0

43.0

43.0

DF50X2-EZRE CR80

22/50

48.2

45.1

48.2

45.1

47.8

44.8

45.3

43.1

24/45

50.2

49.3

50.2

49.3

49.6

48.8

47.1

46.9

26/40

52.3

52.3

52.3

52.3

51.5

51.5

49.0

49.0

DF55X2-EZRE CR80

22/50

54.5

48.8

54.5

48.8

53.4

48.1

50.5

46.3

24/45

56.6

53.7

56.6

53.7

55.3

52.8

52.4

50.9

26/40

58.7

58.7

58.7

58.7

57.2

57.2

54.3

54.3

DF60X2-EZRE CR80

22/50

61.5

54.3

61.5

54.3

59.4

53.0

56.2

51.1

24/45

63.8

59.6

63.8

59.6

61.5

58.1

58.2

55.9

26/40

66.1

65.2

66.1

65.2

63.5

63.3

60.2

60.2

Technical Data Downflow Units X Type

Performance Data

Standard Condenser

TC = Total Cooling
SC = Sensible Cooling

(1) All data quoted is gross

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (based upon 24°C Dry Bulb)

Outdoor Temperature

-20°C to +41°C