Easicool™ precision air conditioning, Dimensional & installation data, Ins ta lla tio n – Airedale EasiCool 6kW 64kW User Manual

Page 38: Minimum unit clearances, Open & enclosed floorstands option, Backward curved ec fan motor option, Minimum ceiling clearance

Advertising
background image

EasiCool™

Precision Air Conditioning

Dimensional & Installation Data

Minimum Unit Clearances

Open & Enclosed Floorstands Option

A

B

C - Floorstand(3)

Min 200 - Max 750

(+ 50mm Feet

Adjustable +/- 20mm)

D(4)

DF6 - DF10

mm

670

610

Min 300

DF13 - DF17

mm

990

610

Min 300

DF20 - DF26

mm

1310

610

Min 300

DF28 - DF31

mm

1460

700

Min 300 - Max 800

(+ 50mm Feet

Adjustable +/- 20mm)

N/A

DF35 - DF45

mm

1835

700

N/A

DF50 - DF60

mm

2170

700

N/A

Backward Curved EC Fan Motor Option

A

B

C (3)

D(5)

With Feet Only (4)

With Leg & Feet (4)

Min

Max

Min

Max

DF6 - DF10

mm

670

610

284

329

604

1074

Min 300

DF13 - DF17

mm

990

610

362

407

697

1152

Min 300

DF20 - DF26

mm

1310

610

362

407

697

1152

Min 300

DF28 - DF31

mm

1460

700

356

401

686

1146

Min 300

DF35 - DF45

mm

1835

700

356

401

686

1146

Min 300

DF50 - DF60

mm

2170

700

356

401

686

1146

Min 300

Minimum Ceiling Clearance

E

Forward Only

Forward & 1 Side

Forward & 2 Sides

All Faces

DF6 - DF10

mm

470

240

160

120

DF13 - DF17

mm

550

330

240

170

DF20 - DF26

mm

560

370

280

190

DF28 - DF31

mm

620

410

310

210

DF35 - DF45

mm

640

450

350

230

DF50 - DF60

mm

640

480

380

240

(1)

Shown with optional open floor stand.

(2)

Shaded area indicates minimum service and maintenance requirements.

(3)

Dimension C denotes recommended minimum/maximum floorstand height, refer to Airedale for special applications, please specify at order.

(4)

Min = Threaded foot at minimum extension.

Max = Threaded foot at maximum extension.

(5)

Dimension D refers to units fitted with LPHW which require access to the RHS of the unit to set up the regulating valve.

(6)

SERVICES SIDE ACCESS GLAND PLATE, OPTIONAL POSITION; ensure appropriate clearance is available to the base of the RHS of the unit if this option is

selected.

38

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Ins

ta

lla

tio

n

Advertising