Easicool™ precision air conditioning, Te ch nic al x-t yp e df, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual

Page 67: Electrical data

Advertising
background image

EasiCool™

Precision Air Conditioning

DF20X2 - DF26X2

67

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

DF

DF20X2-EZRE-0

DF22X2-EZRE-0

DF26X2-EZRE-0

Standard Condenser Match

1 x CR30

1 x CR50

1 x CR50

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

24

Unit Data Full Function - X

(1)

Nominal Run Amps

A

37.7

38.1

41.1

Maximum Start Amps

A

75.1

75.5

98.0

Recommended Mains Fuse Size

A

50

50

50

Unit Data Cooling Only - X
Nominal Run Amps

(2)

A

16.0

16.4

19.4

Maximum Start Amps

A

53.4

53.8

76.3

Recommended Mains Fuse Size

A

20

20

25

Evaporator Fan - EC Motor Per Fan

Centrifugal Forward Curved DD EC - Designed to 25Pa ESP

Quantity

2

2

2

Maximum Electrical Input Power

(3)

kW

1.15

1.15

1.15

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Compressor - Per Compressor
Quantity x Motor Size

kW

2 x 3.3

2 x 3.3

2 x 4.2

Nominal Run Amps

A

5.6

5.6

7.1

Locked Rotor Amps

A

43

43

64

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity

1

2

2

Maximum Electrical Input Power

kW

0.6

0.6

0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

2

2

2

Number of Elements

6

6

6

Rating

kW

15

15

15

Current per Phase

A

21.65

21.65

21.65

Humidifier
Capacity

kg/hr

3

3

3

Rating

kW

2.25

2.25

2.25

Full Load Amps

A

3.25

3.25

3.25

Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Quantity
Maximum Electrical Input Power

(3)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Quantity

1

1

1

Quantity x Motor Size

(3)

kW

2.55

2.55

2.55

Full Load Amps

A

3.9

3.9

3.9

Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Quantity

1

2

2

Maximum Electrical Input Power

(3)

kW

0.73

0.73

0.73

Full Load Amps

A

3.3

3.3

3.3

Technical Data Downflow Units X Type

Electrical Data

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.