Controls

Password Protection

The control system integrity can be maintained by restricting access with a password PIN number.

CAUTION

IMPORTANT: To change the PIN number, please contact Airedale at time of order with the preferred 4 digit number.

Remote On/Off

Terminals for interlocking are provided to enable or disable the unit remotely.

Fire Shut Down

Terminals for interlocking are provided to shut down the unit in the event of fire.

Compressor Anti-Cycle Control

Programmed to provide automatic anti-cycling delays of up to 10 starts per hour with a minimum off time of 3 minutes.

Compressor Rotation

On tandem compressor units the controller is programmed to provide automatic compressor rotation to ensure equal
compressor running times. In the event of a compressor fault on networked systems the controller is programmed to
automatically select the next compressor in order of running hours.

Compressor Hours Run Log & Reset

Allows the user to monitor the running times of each compressor and reset after maintenance.

Hours run log or visual service indicator provided.

Evaporator Fan Hours Run Log & Reset

Allows the user to monitor the running times of the evaporator fans and reset after maintenance.

Hours run log or visual service indicator provided.

Head Pressure Control and Condenser Fan Speed Controller

Each refrigerant circuit (TEV or EEV) is fitted with condenser pressure transducers and a modulating condenser fan
speed controller to allow the designed head pressure to be monitored and maintained under varying ambient conditions.
Condenser fan speed control settings are input via the display keypad.

Evaporator Fan Speed Controller

(Sizes 6 - 26)

Evaporator fan speed control is easily set via the display keypad and can be incrementally increased

or decreased to meet on site airflow and external static pressure requirements.

Filter Change Alarm

Filter change is managed by the AireTronix software, and is based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value can be adjusted to suit each application and is
factory set to 2000 hours.

Hours run log or visual service indicator provided.

LPHW Frost Protection

(DX units with LPHW option)
The coil temperature sensor is mounted on the DX coil and has a fixed 3°C low limit setting to disable DX cooling.