Easicool™ precision air conditioning, Ins ta lla tio n, Refrigerant charging guide – Airedale EasiCool 6kW 64kW User Manual

Page 44: Unit refrigerant charge

Advertising
background image

EasiCool™

Precision Air Conditioning

44

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Ins

ta

lla

tio

n

Indoor Unit

Standard Condenser

Larger Condenser

(IR)

kg/Circuit

HGRH

(OR)

kg/Circuit

(OR)

kg/Circuit

kg/Circuit

V6X-EZRE

1

1.1

CR12

1.4

CR16

2.7

V8X-EZRE

1

1.1

CR16

2.7

CR22

2.2

V10X-EZRE

1

1.1

CR16

2.7

CR22

2.2

V13X-EZRE

1.5

1.7

CR22

2.2

CR30

4.3

V15X-EZRE

1.5

1.7

CR22

2.2

CR30

4.3

V17X-EZRE

1.5

1.7

CR30

4.3

CR50

4.9

V20X2-EZRE

2.2

2.5

CR30

4.3

CR50

4.9

V22X2-EZRE

2.2

2.5

CR50

4.9

CR65

9.8

V26X2-EZRE

2.2

2.5

CR50

4.9

CR65

9.8

V28X-EZRE

2.7

3

CR50

4.9

CR65

9.8

V28X2-EZRE

2.6

2.9

CR50

4.9

CR65

9.8

V31X-EZRE

2.7

3

CR50

4.9

CR65

9.8

V31X2-EZRE

2.6

2.9

CR50

4.9

CR65

9.8

V35X-EZRE

3.3

3.7

CR50

4.9

CR65

9.8

V35X2-EZRE

3.3

3.7

CR50

4.9

CR65

9.8

V40X-EZRE

3.5

4

CR65

9.8

CR80

8.4

V40X2-EZRE

3.6

4.1

CR65

9.8

CR80

8.4

V45X2-EZRE

4.2

4.7

CR80

8.4

CR105

16.7

V50X2-EZRE

4.5

5.1

CR80

8.4

CR105

16.7

V55X2-EZRE

5.2

5.8

CR80

8.4

CR105

16.7

V60X2-EZRE

5.4

5.9

CR80

8.4

CR105

16.7

Indoor Unit

Standard Condenser

Larger Condenser

(IR)

kg/Circuit

HGRH

(OR)

kg/Circuit

(OR)

kg/Circuit

kg/Circuit

DF6X-EZRE

1

1.1

CR12

1.4

CR16

2.7

DF8X-EZRE

1

1.1

CR16

2.7

CR22

2.2

DF10X-EZRE

1

1.1

CR16

2.7

CR22

2.2

DF13X-EZRE

1.5

1.7

CR22

2.2

CR30

4.3

DF15X-EZRE

1.5

1.7

CR22

2.2

CR30

4.3

DF17X-EZRE

1.5

1.7

CR30

4.3

CR50

4.9

DF20X2-EZRE

2.2

2.4

CR30

4.3

CR50

4.9

DF22X2-EZRE

2.2

2.4

CR50

4.9

CR65

9.8

DF26X2-EZRE

2.2

2.4

CR50

4.9

CR65

9.8

DF28X-EZRE

2.7

3

CR50

4.9

CR65

9.8

DF31X-EZRE

2.7

3

CR50

4.9

CR65

9.8

DF35X-EZRE

3.3

3.7

CR50

4.9

CR65

9.8

DF40X-EZRE

3.5

3.9

CR65

9.8

CR80

8.4

DF45X-EZRE

4.2

4.6

CR80

8.4

CR105

16.7

DF50X2-EZRE

4.5

5

CR80

8.4

CR105

16.7

DF55X2-EZRE

5.3

5.8

CR80

8.4

CR105

16.7

DF60X2-EZRE

5.4

5.9

CR80

8.4

CR105

16.7

Refrigerant Charging Guide

The following information can be used to estimate the refrigerant quantity required in a typical split system installation.

Unit Refrigerant Charge

(kg / Circuit)
The following information can be used to estimate the refrigerant quantity required in a typical split system installation.
The table shows the refrigerant charge / circuit for the indoor and outdoor units.