Technical Data Downflow Units X Type

Performance Data

Standard Condenser

Cooling Capacity (1)

Ambient

Air On

25°C

30°C

35°C

40°C

(DB°C/%RH)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

DF6X-EZRE CR12

22/50

6.3

6.1

6.3

6.1

6.3

6.1

6.0

5.8

24/45

6.6

6.6

6.6

6.6

6.5

6.5

6.2

6.2

26/40

6.9

6.9

6.9

6.9

6.9

6.9

6.6

6.6

DF8X-EZRE CR16

22/50

8.0

7.9

8.0

7.9

8.0

7.9

7.6

7.6

24/45

8.4

8.4

8.4

8.4

8.4

8.4

8.0

8.0

26/40

8.8

8.7

8.8

8.7

8.8

8.7

8.5

8.1

DF10X-EZRE CR16

22/50

10.5

10.4

10.5

10.4

10.3

10.3

9.8

9.8

24/45

11.0

11.0

11.0

11.0

10.8

10.8

10.3

10.3

26/40

11.5

11.5

11.5

11.5

11.3

11.3

10.8

10.8

DF13X-EZRE CR22

22/50

13.6

12.4

13.6

12.4

13.4

12.3

12.7

11.8

24/45

14.1

13.7

14.1

13.7

13.9

13.5

13.2

13.0

26/40

14.7

14.7

14.7

14.7

14.4

14.4

13.7

13.7

DF15X-EZRE CR22

22/50

15.4

14.5

15.4

14.5

15.1

14.3

14.3

13.7

24/45

16.0

15.7

16.0

15.7

15.6

15.4

14.9

14.8

26/40

16.6

16.6

16.6

16.6

16.2

16.2

15.5

15.5

DF17X-EZRE CR30

22/50

17.7

16.5

17.7

16.5

17.5

16.4

16.5

15.8

24/45

18.3

18.0

18.3

18.0

18.0

17.8

17.0

17.0

26/40

18.9

18.9

18.9

18.9

18.5

18.5

17.6

17.6

DF20X2-EZRE CR30

22/50

21.3

19.9

21.3

19.9

20.7

19.4

19.5

18.7

24/45

22.2

21.9

22.2

21.9

21.5

21.3

20.4

20.4

26/40

23.1

23.1

23.1

23.1

22.3

22.3

21.2

21.2

DF22X2-EZRE CR50

22/50

21.9

21.2

21.9

21.2

21.9

21.2

21.1

20.5

24/45

22.9

22.9

22.9

22.9

22.9

22.9

22.0

22.0

26/40

24.0

24.0

24.0

24.0

24.0

24.0

23.0

23.0

DF26X2-EZRE CR50

22/50

26.5

24.2

26.5

24.2

26.5

24.2

25.1

23.3

24/45

27.5

26.5

27.5

26.5

27.4

26.4

26.0

25.4

26/40

28.6

28.6

28.6

28.6

28.4

28.4

27.0

27.0

TC = Total Cooling
SC = Sensible Cooling

(1) All data quoted is gross

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (based upon 24°C Dry Bulb)

Outdoor Temperature

-20°C to +41°C