Easicool™ precision air conditioning, Technical data downflow units wx type, Te ch nic al w x - t yp e df – Airedale EasiCool 6kW 64kW User Manual

Page 99

Advertising
background image

EasiCool™

Precision Air Conditioning

Technical Data Downflow Units WX Type

Noise Data

99

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Te

ch

nic

al

W

X - T

yp

e

DF

Sound

Frequency (Hz) dB

Measurement

Overall

dB(A)

63

125

250

500

1000

2000

4000

8000

DF28WX

Discharge Air

Power

87

77

80

79

81

81

82

79

76

Return Air

Power

68

77

71

63

66

63

58

56

47

Case Breakout

Power

70

80

70

63

67

67

60

57

48

Sound @ 3m

Pressure

55

65

56

49

53

52

45

42

34

DF31WX

Discharge Air

Power

91

78

84

83

85

84

85

83

80

Return Air

Power

71

77

75

66

69

66

61

60

52

Case Breakout

Power

73

80

74

67

70

69

63

60

52

Sound @ 3m

Pressure

58

66

59

52

55

55

48

46

38

DF35WX

Discharge Air

Power

90

77

83

82

87

83

84

82

79

Return Air

Power

71

76

74

65

71

65

60

59

51

Case Breakout

Power

72

78

73

66

71

68

61

60

51

Sound @ 3m

Pressure

58

65

58

51

57

53

47

45

37

DF40WX

Discharge Air

Power

92

80

86

85

89

86

86

85

81

Return Air

Power

73

78

76

67

73

67

62

62

53

Case Breakout

Power

75

80

75

68

74

70

64

62

54

Sound @ 3m

Pressure

60

65

61

54

59

56

49

48

40

DF45WX

Discharge Air

Power

92

80

86

85

89

86

86

85

81

Return Air

Power

73

78

76

67

73

67

62

62

54

Case Breakout

Power

75

80

75

68

74

70

64

62

54

Sound @ 3m

Pressure

60

65

61

54

59

56

49

48

40

DF50WX2

Discharge Air

Power

89

78

84

86

82

83

84

81

76

Return Air

Power

69

76

75

69

66

64

59

58

48

Case Breakout

Power

71

79

74

69

67

68

61

58

49

Sound @ 3m

Pressure

56

64

59

55

52

53

47

43

34

DF55WX2

Discharge Air

Power

89

78

84

86

82

83

84

81

76

Return Air

Power

70

77

75

69

67

64

60

58

48

Case Breakout

Power

71

79

74

69

68

68

62

58

49

Sound @ 3m

Pressure

57

64

59

55

53

53

47

44

35

DF60WX2

Discharge Air

Power

91

80

85

89

84

85

86

83

79

Return Air

Power

71

79

76

72

69

66

62

60

51

Case Breakout

Power

73

81

75

73

69

69

63

60

52

Sound @ 3m

Pressure

58

66

60

58

55

54

49

46

37

(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.

Advertising