Calculation of System Refrigerant Charge (kg)

The system refrigerant charge can be calculated using the following equation:

SR = LR + IR + OR

Where:

SR

=

Total System Refrigerant Charge (kg)

LR

=

Total Liquid Line Refrigerant Charge. (As calculated from above)

IR

=

Indoor Unit Refrigerant Charge.

OR =

Outdoor Unit Refrigerant Charge.

Example

Indoor Unit Model Ref. = DF10X-EZRE
Outdoor Unit Model Ref = CR16 Condenser
Interconnecting Pipework = 10 metres

From the Refrigerant Pipe Sizing Guide, the
liquid line size given for pipework length of 10
metres is:0.05kg/m

SR = LR + IR + OR

Where:

LR = L x m

LR

= 0.5 kg. (As calculated from above)

IR

= 1.0 kg

OR = 2.7 kg

SR = 0.5 + 1.0 + 2.7

Therefore

Calculation of Liquid Line Refrigerant Charge (kg)

The liquid line refrigerant charge can be calculated using the following equation:

LR = L x m

Where:
LR

=

Total Liquid Line Refrigerant charge (kg)

L

=

Length of Interconnecting pipework (metres)

m

=

Liquid Line Refrigerant charge / metre. Refer to Liquid Line

Refrigerant Charge (kg/m), above.

Where:
L

=

10 metres

m

=

0.05 kg/m (Liquid

Line Size = 3/8”)

LR =

10 x 0.05 = 0.5kg

System Refrigerant Charge

System Refrigerant
Charge

= 4.2 kg / Circuit