EasiCool™

Precision Air Conditioning

Interconnecting Wiring

L1

 

L2

 

L3

 

N

 

PE

 

INDOOR UNIT

C1

 

 

L1

N1

 

 

N

PE

 

 

PE

833

 

 

833

500

 

 

500

SCR

 

 

SCR

L1

 

L2

 

INDOOR UNIT

L3

 

N

 

PE

 

Mains Incoming Supply

400V / 3PH + N / 50Hz

OUTDOOR

UNIT

Mains sub fused supply to Outdoor Unit

(must be wired from Indoor Unit)

Fan Speed Control Signal to Outdoor Unit

(only applicable for EC fan based Outdoor Units)

Mains Incoming Supply

400V / 3PH + N / 50Hz

560

 

Common Alarm Normally Open

561

 

Common

562

 

Common Alarm Normally Closed

INDOOR UNIT

583

 

Fire Detection

502

 

24Vac

560

 

Non-Critical Alarm Normally Open

561

 

Common

562

 

Non-Critical Alarm Normally Closed

563

 

Critical Alarm Normally Open

INDOOR UNIT

564

 

Common

565

 

Critical Alarm Normally Closed

583

 

Fire Detection

502

 

24Vac

522

 

Remote On/Off

502

 

24Vac

Rx-Tx-  

Rx+Tx+  

GND

 

Rx-Tx-  

Rx+Tx+  

GND

 

INDOOR UNIT

Network Connections (Inward connection)

Network Connections (Outward connection)

INDOOR UNIT

X Models (Matched

System)

WX Models (Non-Matched

System)

X and WX Models

Indoor Controls Only

Sizes 6-26

Sizes 28-60

54

EasiCool Technical Manual 7525389 V1.1.0_02_2013