- 42 -

APPLICATIONS

Space Heating Applications

WARNING

• Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol group

must not be introduced into the system when used for open loop potable water and
space heating.

• The T-M32 can be used to supply potable water and space heating and shall not be

connected to any heating system or component(s) previously used with non-potable
water where any chemicals were added to the water heating appliances.

• When the system requires water for space heating at temperatures higher than required

for other uses, a means such as a mixing valve shall be installed to temper the water for
those other uses in order to reduce scald hazard potential.

• Water temperature over 125 °F can cause severe burns instantly or death from scalds.
• Chemicals such as diluted Glycol can be used for radiant floor, Hydro/fan coil air or

Baseboard heating only. The diluted solution of glycol must contain between 25% and
55% of Glycol. Be aware that in closed-loop glycol systems, low pressure in the heat
exchanger can cause low-temperature boiling, resulting in excessive noise and damage
to the water heater. Consult with the glycol maker for specifications prior to use.

Re-circulation:














This is a concept drawing only.

* Size the pump to provide at about 2 GPM through the
system at 15 Ft of Head plus applications and piping head
losses. 2 GPM will allow the system to operate at its
optimal performance.

* If the application requires a higher re-circulating flow rate,
make sure that the re-circulating flow rate is no greater
than 4 GPM
. If the flow rate is too high, the system could
be damaged by erosion.