3) connecting pi485 – bacnet gateway, 18 bacnet gateway, How to install – LG PQNFB17B0 User Manual

Page 18: Multi v tx rx, Multi v, Multi v shield line of 0.75 mm

Advertising
background image

How to install

18 BACnet Gateway

(3) Connecting PI485 – BACnet Gateway

1. When connecting two or more PI485s to one BACnet Gateway, connect each BUS-A/BUS-B of

other PI485s to be connected to BUS-A/BUS-B of the PI485.

2. Connect the BUS-A of the PI485 to the TX of the BACnet Gateway and the BUS-B to the RX.

• Connect LG-NET 1~4 to any of the BACnet Gateway. (Connect the LG-NET to the RS-485 port)
• 64 outdoor units at maximum can be connected to each 485 port of the BACnet Gateway and the

number of indoor units to be connected to the BACnet Gateway is 256 at maximum.

Note: Disconnect the connector from the 485 port of the BACnet Gateway, connect the BUS-A to

the TX and the BUS-B to the RX by using the (-) driver, and then connect the connector to the
485 port of the BACnet Gateway. Because the 485 communication line has a polarity, connect
the line correctly.

LG-NET 1

MENU/

SELECT

TX
RX

LG-NET 2

TX
RX

LG-NET 3

TX
RX

LG-NET 4

TX
RX

Ethernet 1

ACT
LNK

Ethernet 2

ACT
LNK

Console

Run

Power

TX
RX

Ext 1

TX
RX

Ext 2

TX
RX

DI

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

DO

1

2

3

4

ON

L1 2 3 4

KSDO4H

Multi V

TX

RX

ON

L1 2 3 4

KSDO4H

Multi V

ON

L1 2 3 4

KSDO4H

Multi V

Shield line of 0.75 mm

2

(RS-485 communication line)

1

2

BACnet Gateway side

PI485 side

BUS-A

TX

RX

BUS-B

PI485

PI485

PI485

PI485

PI485

PI485

PI485

Advertising