58 bacnet gateway – LG PQNFB17B0 User Manual

Page 58

Advertising
background image

Objects (BACnet/IP)

Point

No.

Name

ObjectName Product Name

(XXX : Unit address)

Object

Type

Unit

Inactive

Active

Text-0

Text-1

Text-2

Text-3

Text-4

Text-5

19

Set Temperature (status)

SetTempStatus_XXX

AI

°C

20

-

-

-

21

AC Operation Mode (setting)

HrvModeCommand_XXX

MO

Cool

Auto

Heat

22

AC Operation Mode (status)

HrvModeStatus_XXX

MI

Cool

Auto

Heat

23

AC ON/OFF (setting)

HrvStartStopCommand_XXX

BO

Stop

Run

24

AC ON/OFF (status)

HrvStartStopStatus_XXX

BI

Stop

Run

25

AC Humidify (setting)

HrvHumidifyCommand_XXX

BO

Off

On

26

AC Humidify (status)

HrvHumidifyStatus_XXX

BI

Off

On

58 BACnet Gateway