Monitoring and Controlling point of indoor and ventilator

Functional Specifications BACnet Gateway

Applicable monitoring and controlling point for the indoor and ventilator are listed below.

Object Name's XX is indoor's address number.

Name

Object Name

Object Type

Indoor

Vent

1

Run/Stop (setting)

StartStopCommand_XXX

Binary Output

O

O

2

Run/Stop (status)

StartStopStatus_XXX

Binary Input

O

O

3

Lock (setting)

LockCommand_XXX

Binary Output

O

O

4

Lock (status)

LockStatus_XXX

Binary Input

O

O

5

Filter Sign

FilterSign_XXX

Binary Input

X

O

6

Filter Sign reset

FilterSignReset_XXX

Binary Value

X

O

7

Operation Mode (setting)

ModeCommand_XXX

Multistate Output

O

O

8

Operation Mode (status)

ModeStatus_XXX

Multistate Input

O

O

9

Swing (setting)

SwingCommand_XXX

Binary Output

O

X

10

Swing (status)

SwingStatus_XXX

Binary Input

O

X

11

Fan speed (setting)

FanSpeedCommand_XXX

Multistate Output

O

O

12

Fan speed (status)

FanSpeedStatus_XXX

Multistate Input

O

O

13

Set Room Temperature

SetRoomTemp_XXX

Analog Value

O

X

14

Room Temperature

RoomTemp_XXX

Analog Input

O

X

15

Alarm

Alarm_XXX

Binary Input

O

O

16

Error Code

MalfunctionCode_XXX

Analog Input

O

O

17

User Mode(setting)

UserModeCommand_XXX

Multistate Output

X

O

18

User Mode(status)

UserModeStatus_XXX

Multistate Input

X

O

19

Set Temperature (status)

SetTempStatus_XXX

Analog Input

O

X

20

Accumulator Power Distribution
(status)

AccumPowerStatus_XXX

Analog Input

O

X

21

AC Operation Mode (setting)

Hrv_ModeCommand_XXX

Multistate Output

X

O

22

AC Operation Mode (status)

Hrv_ModeStatus_XXX

Multistate Input

X

O

23

AC ON/OFF (setting)

HrvStartStopCommand_XX
X

Binary Output

X

O

24

AC ON/OFF (status)

HrvStartStopStatus_XXX

Binary Input

X

O

25

Humidify (setting)

HrvHumidifyCommand_XXX

Binary Output

X

O

26

Humidify (status)

HrvHumidifyStatus_XXX

Binary Input

X

O

27

Set Upper Temperature (setting)

SetUpperTempCommand_X
XX

Analog Value

O

X

28

Set Lower Temperature (setting)

SetLowerTempCommand_X
XX

Analog Value

O

X

29

Set Upper Temperature (status)

SetUpperTempStatus_XXX

Analog Input

O

X

30

Set Lower Temperature (status)

SetLowerTempStatus_XXX

Analog Input

O

X

31

Mode Lock (setting)

ModeLockCommand_XXX

Binary Output

O

X

32

Mode Lock (status)

ModeLockStatus_XXX

Binary Input

O

X

Installation/Owner Manual 51