74 modbus – LG PQNFB17B0 User Manual

Page 74

Advertising
background image

Objects (Modbus-TCP)

• Case AHU

Function Code

Device No.

Product No.

Point

Instance No.

Name

1

0

0

0

0x08000

ON/OFF status

5

0

0

0

0x08000

ON/OFF setting

1

0

1

0

0x08010

ON/OFF status

5

0

1

0

0x08010

ON/OFF setting

1

1

0

0

0x08100

ON/OFF status

5

1

0

0

0x08100

ON/OFF setting

3

0

0

0

0x48000

Mode status

6

0

0

0

0x48000

Mode setting

3

0

1

0

0x48010

Mode status

6

0

1

0

0x48010

Mode setting

3

1

0

0

0x48100

Mode status

6

1

0

0

0x48100

Mode setting

74 Modbus

Advertising