Objects (Modbus-TCP)

Modbus Point List : AHU

Function Code : 0x01 and 0x05

Address

Register

F

unction Name

Object Name

(XXX : Unit address)

Inactive Active

0x0000 1

Coil Read

ON/OFF StartStopStatus_XXX

Stop

Run

0x0001 2

L

OCK

LockStatus_XXX

Permit

Prohibit

0x0002 3

FILTER

SIGN

FilterSign_XXX

Off

On

0x0003 4

S

MOKE

FireAlarmStatus_XXX

Stop

Run

0x0004 5

HUMIDITY

HumidifyStatus_XXX

Stop

Run

0x0005 6

A

UTO

VENT

AutoVentStatus_XXX

Stop

Run

0x0006 7

HUMIDIFIER

HumidifiyUnitStatus-XXX

Stop

Run

0x0007 8

H

EATER

HeaterUnitStatus_XXX

Stop

Run

0x0008 9

VENT

FAN

VentFANStatus_XXX

Stop

Run

0x0009 10

SUPPLY

FAN

SupplyFANStatus_XXX

Stop

Run

0x000A 11

ALARM

Alarm_XXX

Normal

Abnormal

0x0000 1

Write Single Coil

ON/OFF StartStopCommand_XXX

Stop

Run

0x0001 2

L

OCK

LockCommand_XXX

Permit

Prohibit

0x0003 4

S

MOKE

FireAlarmCommand_XXX

Stop

Run

0x0004 5

HUMIDITY

HumidifyCommand_XXX

Stop

Run

0x0005 6

A

UTO

VENT

AutoVentCommand_XXX

Stop

Run