Systems Insight Manager integration 114

To register the MIB:

1.

Copy the MIB to the HP\Systems Insight Manager\mibs folder.

2.

From the HP\Systems Insight Manager\mibs folder, run mcompile cpqpower.mib from the

command line to compile the new MIB. A new file named cpqpower.cfg is created.

3.

Register the new MIB by entering mxmib -a cpqpower.cfg from the HP\Systems Insight

Manager\mibs command line.

4.

Enter HP\Systems Insight Manager\mibs>mxmib at the command line and verify that the

new MIB is listed.

NOTE:

For more information on uploading and registering a MIB in HP SIM, refer to the HP

Systems Insight Manager Technical Reference Guide located on the HP Management CD.

Configuring the management module to send traps
to HP SIM

1.

Add the HP SIM server as an SNMP trap recipient on the SNMP Traps tab (on page

69

).

2.

Configure the management module to send alert notifications to HP SIM on the Events tab (on page

67

).