Manual control menu – HP UPS Management Modules User Manual

Page 55

Advertising
background image

HP UPS Management Module web interface 55

Click Help to view online help.

Manual Control menu

Click Manual Control in the left navigation frame to display the Manual Control screen. This screen
contains manual commands such as Initiate Battery Test and Restart Management Module.

NOTE:

Depending on the specific UPS model, this screen will vary.

The Initiate Battery Test option is not available for all UPSs. To initiate a UPS battery test:

CAUTION:

Selecting this option might result in an ungraceful shutdown.

IMPORTANT:

Do not run a battery test while the UPS is On Battery.

1.

Select Initiate Battery Test.

2.

Click Execute Command. The results of the test appear on the Parameters screen ("

Parameters menu

"

on page

52

) in the Test Results Summary field, and a log entry is created in the Application Log

("

Application Log menu

" on page

58

).

To reset the management module:

1.

Select Restart Management Module.

2.

Click Execute Command.

NOTE:

Restarting the management module does not drop the UPS load. The web interface is

not available while the management module restarts.

Click Help to view online help.

Advertising