WARNING: All power wires connecting to AURORA inverter must
have a section of at least 14 AWG (2.5mm

2

) and must be able to operate

at temperature of at least 90 °C. All wiring must be sized in accordance

with the National electrical standards and applicable local codes. The
wire size may need to be increased due to temperature, wire length and
conduit fill factors. The wiring should be rated for wet location, UV
sunlight-resistant and outdoor location. Consult with a qualified electrical
designer when determining system wiring.
Minimum MPPT input connection Dc wire size, 12 AWG, 20 Amps.
Minimum Ac wire size, 12AWG, 16 Amps.
Maximum MPPT input wire and AC wire size is 10 AWG strand wire

The AURORA must be installed using watertight wiring methods. This requires
the use of UL listed watertight components and locknuts with the applicable
wiring method. On the bottom of the unit there are four 29mm diameter holes
(Trade size 3/4") covered with cap Elektrozubehör, type H 400 P (model
designation K 426 21 P) or equivalent UL listed watertight cap. Un-used holes
shall be left sealed by the caps. Fig.11 shows an example of hole assignment.


WARNING: It is the installer responsability to make the conduit
connection watertight, by using the properly listed components and
locknuts, and by applying the correct tightening torque.

Fig.11: Position of the holes on the bottom side

DC from Wind
Interface box

DC From Wind
Interface Box

Fan & RS485 Serial Link

Grid