Step 1/7: Open the Ac disconnect switch or circuit breaker and lockout the

Ac disconnecting means.

Step 2/7: Open the Dc disconnect switch and lockout the Dc disconnecting

means.

Step 3/7: Verify there is no voltage on the connection terminals.

Step 4/7: Connect AURORA to the Main Ground (Protective Earth)

The input and output circuits are isolated from the enclosure.
The plant must have a Protective Earth (Equipment main ground)
connection as required by the National Electric Code ANSI/FNPA 70
for proper equipment ground conductor sizing. The Protective Earth
cable must be connected to the AURORA chassis ground connection as
shown in Fig.14 using the screw provided. Tighten the screw to a torque
of 0.6 Nm (5.3 in-lbs).

Fig.13: Location of Main Ground PE Screw

Ground point