Mounting the HUB Communications Manager

The GSLC provides mounting holes to support a HUB Communications Manager.

Figure

25

Mounting the HUB Product to the GSLC Enclosure

To mount the HUB Communications Manager to the side of the GSLC enclosure:

1. Locate the mounting holes on the side of the GSLC enclosure as shown in Figure 11 on page 16.

2. Remove the knockouts and add bushings.

3.

Align the HUB (vertically) over the mounting holes with the HUB product’s ports facing forward.

4. Insert the mounting screws from the outside into the GSLC enclosure. The mounting screws are provided

with the HUB product.

5. Tighten until secure, but do not over-tighten.

6. Install CAT5 cabling as needed.

7. Install the protective shield for the HUB product.

Mounting

Screw

Mounting

Screw