AC Wiring

WARNING: Shock Hazard

Ensure all circuit breakers or disconnect devices are turned off or disconnected before

wiring. Make certain the inverter and other active devices are turned off or disabled

before wiring.

Split-Phase Wiring

The GSLC can have multiple terminal bus bars for multiple AC connections. Because the Radian

inverter possesses two sets of AC input connections and one set of output connections, up to three
TBB sets are available. Each set of bus bars are paired in red and black, for the 120/240 Vac

connections required by the Radian inverter.

The TBB set on the left is generally used for the inverter’s AC output connections. The central TBB set

is for utility grid connections and the right TBB set is for a generator. The preassembled GSLC models

follow this convention.
Each TBB accepts conductors from 1/0 (70 mm

2

) to #14 AWG (2.5 mm

2

). See Table 2 on page 29 for

required torque values.
If steps are inappropriate for a given system (such as instructions for a generator when none is

present), they can be ignored.

Figure

33

AC Terminal Bus Bars (split-phase)

AC Output

Grid

Generator

Neutral

To make the external AC connections to the
split-phase GSLC:

1. Connect the L1 wire from the AC load panel

to black TBB

1

(AC OUT - HOT LEG 1).

Connect the L2 wire from the AC load panel
to red TBB

2

(AC OUT - HOT LEG 2).

2. Connect the neutral wire from the AC load

panel to neutral TBB

3

.

3. Connect the L1 wire from the utility grid

panel (if present) to black TBB

4

(GRID IN - HOT LEG 1). Connect the L2 wire
from the utility grid panel to red TBB

5

(GRID IN - HOT LEG 2).

4. Connect the neutral wire from the utility

grid panel (if present) to neutral TBB

3

.

5. Connect the L1 wire from the generator

(if present) to black TBB

6

(GEN IN - HOT

LEG 1). Connect the L2 wire from the
generator to red TBB

7

(GEN IN - HOT LEG 2).

6. Connect the neutral wire from the generator

(if present) to neutral TBB

3

.

NOTE: Remove the neutral-ground bond if
necessary. See page 30.

1

2

3

4

5

6

7