Bypass switches, E 42, R figure 38 – Outback Power Systems GS Load Center Installation Manual User Manual

Page 44: Installation

Advertising
background image

Installation

42

900-0123-01-00 Rev C

Figure 38

Maintenance Bypass Wiring (single-phase)

Multiple-Inverter Installations (Stacking Inverters)

When multiple Radian inverters are stacked for additional power, the basic wiring is repeated for each

inverter. However, several factors need to be considered.

One GSLC is required for each Radian inverter. A single GSLC cannot be sized to handle the requisite current

for multiple Radian inverters.

If more than two Radian inverters are installed, it is recommended to install a separate distribution panel to
distribute incoming power to each GSLC individually. It may be advisable to install separate AC distribution

panels to distribute input and output power to each GSLC.

The GSLC maintenance bypass assemblies cannot be used when more than one Radian inverter is stacked.
See the next section.

Bypass Switches

Inverter systems are often equipped with maintenance bypass switches or interlocks. If the inverter

system ever needs to be shut down or removed, its AC sources and loads must be disconnected. A
bypass device allows the AC source to “bypass” the inverter and deliver power directly to the loads.

This can minimize disruption to the system and it avoids the need for extensive rewiring.

WARNING: Shock Hazard or Equipment Damage

Bypassing multiple sources will usually connect the sources to each other, which may
damage one or both sources. It can otherwise result in power being routed to
inappropriate places.

The bypass assembly does not disconnect the inverter’s AC input. Even with the
inverter bypassed, any AC input source may be a shock hazard unless disconnected.

To wire the GS-IOB-230VAC

after installation:

1. On the disconnect for the AC

source that will be used during
bypass, install a wire from the
left side as shown by

1

.

Connect it to the input bypass
switch as shown by

2

.

2. Install a wire on the right side of

the input bypass switch as
shown by

3

. Connect it to the

right side of the output switch
as shown by

4

.

Output

Inverter Bypass

AC Source

1

2

3

4