Wiring, Grounding, E 29 – Outback Power Systems GS Load Center Installation Manual User Manual

Page 31: Ge 29

Advertising
background image

Wiring

900-0123-01-00 Rev C

29

Wiring

Table 2 Terminal Bus Bar (TBB) Wire Size and Torque Requirements

Conductor Size

Torque Requirements

AWG

mm²

In-lb

Nm

#14 – #10

2.5 – 4

20

2.3

#8

6 – 10

25

2.8

#6– #3

16 – 25

35

4.0

#2

35

40

4.5

#1 – 1/0

50

50

5.7

Grounding

WARNING: Shock Hazard

The unit must be connected to a permanent wiring system that is grounded

according to the IEC 60364 TN standard.

Make sure that no more than one bond is present in the AC system at any time.

Some codes require the bond to be made at the main panel only.

For safety, the neutral and ground conductors should be mechanically bonded.

The GS Load Center (GSLC) is equipped with a neutral-ground bond. If bonding is

required to be in another location, the bond in the GSLC may need to be removed.

Some generators have a neutral-ground bond. When establishing a single bond

elsewhere, it may be necessary to check for a generator bond.

WARNING: Shock Hazard

For all installations, the negative (–) battery conductor should be bonded to the

grounding system at only one point.

The GSLC comes equipped with a negative-

ground bond. This bond may need to be disconnected. If the OutBack GFDI is present, it
can provide the bond. See page 30.

IMPORTANT:

Most OutBack products are not designed for use in a positive-grounded system. If it is
necessary to build a positive-grounded system with OutBack products, contact OutBack

Technical Support at

+1.360.618.4363 before proceeding. Additionally, consult the

online forum at

www.outbackpower.com/forum/, where this subject has been

discussed extensively.

Figure 26

Grounding

The GSLC’s grounding terminal bus bar ( TBB), which is

bonded to the GSLC chassis, is located to the lower left of

the main inverter disconnect. It accepts conductor sizes

from 1/0 to #14 AWG (50 mm down to 2.5 mm).
This TBB accepts ground connections from the Radian
inverter, FLEXmax charge controllers, the OutBack GFDI, the

Grounding Electrode Conductor (GEC) or external earth

ground, and other equipment.
See the Radian Series Inverter/Charger Installation Manual for

recommendations on ground conductor sizing. Once the

size is determined, see Table

2 for required torque values.

Ground TBB