Bonding

All GSLC models are equipped with a mechanical bond between AC

neutral and ground.

All models that do not include the GFDI are also equipped with a mechanical bond between DC

negative and ground. These can be useful in stand-alone systems where no other bond is provided.

If other bonds are present, or if the GFDI is installed later, the GSLC bonds need to be removed.

WARNING: Shock Hazard

If the GFDI is manually installed (see page 24 and the GFDI manual), the negative-ground

bond on the GSLC must be removed. This must also be done if any other PV ground-fault

device is present that establishes its own negative-ground bond. GSLC models purchased

with the OutBack GFDI do not have a bond between negative and ground.

`

Figure

27

Removing Bonding Connections

The GSLC’s

neutral bus bar is located in

the lower right portion of the GSLC.

The neutral-ground bond is established

at one end of the bar, near the base of

the GSLC.

To remove either of the bond connections:

1. Using a Phillips screwdriver, remove the screw

shown above.

2. Remove the metal standoff beneath the bus

bar. The screw and bus bar provide the

mechanical bond to the chassis ground.

3. Rotate the TBB mount. Insert the bus bar into

the open end of the TBB mount so that the TBB
mount supports the bus bar. It may be

necessary to loosen the TBB mount screw

before rotating it.

4. Retighten the screw to secure the TBB mount.

The GSLC’s

negative (–) bus bar is located

near the top of the GSLC. It is attached to

the inverter negative (–) bus and its shunt.

NOTES:

If the TBB is connected directly to

the enclosure by a screw, then the

bond is connected.

If the TBB is held by the TBB mount

and the TBB mount is secured to the

enclosure, the bond is disconnected.

The installed Neutral TBB has white

insulators. A second Neutral TBB with

blue insulators is included in the kit

for locations where blue is standard.

Screw

TBB

Mount

TBB

Mount

Neutral-Ground Bond

Negative-Ground Bond

Bottom of GSLC

Standoff

Standoff

Inverter

Negative (–)

Bus Bar

Top of GSLC

Screw