Applications, Space heating applications warning, Re-circulation – State GTS-710-PIEA User Manual

Page 41

Advertising
background image

- 41 -

Check valve

Check valve

Air 
separator

Recirculation 
pump 

Hot water outlet to 
fixtures

Air Vent

Unions 

Gas supply 

Ball valves 

Expansion tank 

Y‐Strainer 

Cold water 
inlet 

Hot
Water
Outlet

S

Cold
Water
Inlet

Gas
Inlet

APPLICATIONS

Space Heating Applications

WARNING

In order  to purge air in water pipes within a closed-loop system, an air vent and

air separator

  should be installed in to the system. Required circulation flow rates

are labeled next to each application diagram. These

  flow rate requirements must

be followed.

 Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol groups

must not be introduced into the system if the system incorporates an open-loop potable
water system.

 Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol group

must not be introduced into the system when used for open loop potable water and
space heating.

 The water heater can be used to supply potable water and space heating and shall not

be connected to any heating system or component(s) previously used with non-potable
water where any chemicals were added to the water heating appliances.

 When the system requires water for space heating at temperatures higher than required

for other uses, a means such as a mixing valve shall be installed to temper the water for
those other uses in order to reduce scald hazard potential.

 Water

temperature

over

125

F (52ºC) can cause severe burns instantly or death from

scalds.

 Chemicals such as diluted Glycol can be used for radiant floor, Hydro/fan coil air or

Baseboard heating only. The diluted solution of glycol must contain between 25 and
55% of Glycol. Be aware that in closed-loop glycol systems, low pressure in the heat
exchanger can cause low-temperature boiling, resulting in excessive noise and damage
to the water heater. Consult with the glycol maker for specifications prior to use.

Re-circulation:











This is a concept drawing only.

* The recirculation pump is to be controlled by: 
‐Dual‐set aquastat (recommended w/timer) 

OR 

‐“Pump Control Connections”. Refer to p.21. 
 
* The recirculation pump is to provide no less 
than 2 GPM and no more than 4 GPM through 
each activated unit in the system. 