Outdoor installation – State GTS-710-PIEA User Manual

Page 8

Advertising
background image

- 8 -

The dark square is the direction
the dipswitch should be set to.

1
2
3
4
5
6
7
8

TMP1
TMP2
TMP3
MODE
DIRE

OUT

D-PRT

MST

O N

Keep the clearances.

OUTDOOR INSTALLATION

1. Follow all local codes, or in the absence of local codes, follow the most recent edition of

the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA or CAN/CSA B149.1
Natural Gas, Propane Installation Code in Canada.

2. Install outdoors only in areas with mild, temperate climates.

3. Ensure that the unit is set for outdoor installation. Locate the left bank of dipswitches to

the bottom of the 7-Seg. LED on the computer board. The ‘OUT’ dipswitch on that
bank should be switched to its ‘ON’ (right) position (Do not adjust the right bank of
dipswitches).


















4. The outdoor vent cap must be used when unit is installed outdoor. The manufacturer

requires the use of its part No. 9007676005 (TM-VC32).

5. When installed outdoors, the water heater shall be wall-mounted or mounted on a stand.

Locate the water heater in an open, unroofed area and maintain the following minimum
clearances:



Make sure power to the unit is
turned OFF before changing
the dipswitch settings.

Left Bank of Dipswitches

7-Seg LED

Left bank of
dipswitches

Right bank of
dipswitches

There is a 2” clearance from the
left and right sides of the unit to
combustible and non-combustible
surfaces. However, if any portion
or area of the surface is exposed
to the exhaust fumes (i.e. directly
to the sides of the vent cap), that
surface must be at least 24”
away.

Bottom 12”

*

Front 24”

Front 4”

(24” Recommended

for Maintenance)

Back 1”

Side 2”

Side 2”

Top 36”

*

Side 24”

*

Side 24”