Supplemental Characteristics

Table A-2 lists the supplemental characteristics, which are not warranted but are descriptions of typical
performance determined either by design or type testing.

Table A-2. Supplemental Characteristics

Parameter

Agilent 6814B

Agilent 6834B

Agilent 6843A

AC Input Voltage Range:

180

235 Vac (3-phase) or

360

440 Vac (3-phase)

AC Input Frequency:

47

63 Hz

Output Isolation Voltage:

300 Vrms

Maximum Input Current (rms):

18 A low range

10 A high range

24 A low range

15 A high range

24 A low range

15 A high range

Maximum Input Power:

5.8 kVA/4.1 kW

8.9 kVA/5.9 kW

8.9 kVA/5.9 kW

Average Programming Accuracy:

0.2% + 80 mA

0.2%+40mA (3-phase)

0.2%+80mA (1-phase)

0.2% + 80 mA

Average Programming Resolution

rms Voltage:

80 mV

80 mV

80 mV

Overvoltage Programming (OVP):

2 V

2 V

2 V

rms Current:

5 mA

2.5 mA (3-phase)
7.5 mA (1-phase)

7.5 mA

Output Frequency:

10

µ

Hz

10

µ

Hz

10

µ

Hz

Phase (Agilent 6834B in 3-phase mode):

N/A

0.001

°

(45Hz

1kHz)

N/A

Average Measurement Resolution

rms Voltage:

10 mV

10 mV

10 mV

rmsCurrent:

3 mA

6 mA (3-phase)
2 mA (1-phase)

6 mA

List Dwell Time

0

4.30133 x 10

5

s

0

1.07533 x 10

6

s

0

4.30133 x 10

5

s

Triggering Accuracy with Respect to Phase
Synchronization:

100

µ

s

250

µ

s

100

µ

s

Trigger In Response Time:

200

µ

s

400

µ

s

200

µ

s

Minimum Resolution for Dropout:

500

µ

s

Output Response Time:
(output change from 10 to 90% or 90 to 10% of its
total excursion with full resistive load)

50

µ

s

Remote Inhibit Response Time:

<1 ms

Remote Sense Capability:

Up to 10 Vrms can be dropped across each load lead.

Waveform Table Resolution (voltage):

1024 points

Harmonic Measurement Time (amplitude):

1 harmonic

100 ms;

all 50 harmonics

2 s

RS-232 Interface Capabilities

Baud Rates:

300, 600, 1200, 2400, 4800, 9600

Data Format:

7 bits even or odd parity; 8 bits without parity

Language:

SCPI (Standard Commands for Programmable Instruments),

Elgar 9012 PIP

Trig In/Trig Out Characteristics

Trig Out (HC TTL output):

Vol = 0.8 max. @ 1.25 mA

Voh = 3.3 V max. @ 1.25 mA

Trig In (10k pullup):

Vil = 0.8 V max.

Vih = 2 V max.

Advertising