Connections and Wiring

25

NetLinx Integrated Controllers

A metal commoning strip is supplied with each Integrated Controller to connect multiple

relays.

Relay connections

Use A for common and B for output (FIG. 14). Each relay is isolated and normally open. A metal

connector strip is also provided to common multiple relays.

Input/Output (I/O) Connections and Wiring

The I/O port responds to either switch closures, voltage level (high/low) changes, or can be used for

logic-level outputs.

You can connect up to eight devices to the I/O connectors on the NI-4000/3000 (four on the

NI-2000) (FIG. 15). A contact closure between GND and an I/O port is detected as a Push. When

used for voltage inputs, the I/O port detects a low (0-1.5 VDC) as a Push, and a high (3.5-5 VDC)

signal as a Release. When used for outputs, the I/O port acts as a switch to GND and is rated at 200

mA @ 12 VDC. The PWR pin (+12 VDC @ 200 mA) is designed as a power output for the PCS2

or VSS2 (or equivalent). The GND connector is a common ground and is shared by all I/O ports.

The following table lists the wiring specifications for the I/O connectors.

+12V - 12 VDC power output for PCS Power Current Sensors, VSS2 Video Sync

Sensors, or similar I/O-type equipment

I/O 1 - 8 - Up to 8 I/O ports (NI-4000/3000) and up to 4 I/O ports (NI-2000)

(see table below)

GND - Common ground shared with I/O ports 1 - 8 (refer to the following chart)

FIG. 14 RELAY connector (male) (NI-4000/3000/2000)

FIG. 15 INPUT/OUTPUT connector (male)

2

4

A

B

3

B

A

B

1

A

A B

RELAYS (Port 4)

RELAYS (Port 8)

B

6

A

8

B

B

B

7

A

5

B

A

A

4

B A

A

3

A

2

B

1

A

B

NI-4000/NI-3000 relay connector

configuration (Port 8)

NI-2000 relay connector

configuration (Port 4)

I / O (Port 17)

4

+12V

7

8

6 5

GN

D

2

3

1

I / O (Port 9)

4

+1

2V

2

3

1

GND

NI-4000/NI-3000 I/O connector

configuration (Port 17)

NI-2000 I/O connector

configuration (Port 9)