Protocol Description and Timings

Elektronik-Systeme Lauer, MAEN976

17

Conditions for Response Message

The conditions for a response message generated by the monitor are described below:

Delayed Response

If a monitor receives a SCOM message with a broadcast address from the RS485 in-
terface and the command is completed, the generated response message is sent after
a delay time. This is required, because many monitors can be attached to the RS485
bus, but only one monitor can claim the line for its communication. The delay guar-
antees that each response message is sent one after one, even if all monitors have re-
ceived the broadcast message and processed it at the same time, avoiding a collision
on the RS485 bus.

The length of the delay time depends on the monitor address and maximum length
of a response message, and is calculated according to the following formula:

Interface

Address condition

Command status

Response

RS232

Address does not match
monitor address

not EXECUTED

No response

not EXECUTED

No response

Address matches monitor
address

if COMPLETED

ACK

if FAILED

NAK

Address is Broadcast
address (0xFF)

if COMPLETED

ACK

if FAILED

NAK

RS485

Address does not match
monitor address

not EXECUTED

No response

not EXECUTED

No response

Address matches monitor
address

if COMPLETED

ACK

if FAILED

NAK

Address is Broadcast
address (0xFF)

if COMPLETED

Delayed ACK

if FAILED

No response

Ethernet

Address does not match
monitor address

not EXECUTED

No response

not EXECUTED

No response

Address matches monitor
address

if COMPLETED

ACK

if FAILED

NAK

Address is Broadcast
address (0xFF)

if COMPLETED

No response

if FAILED

No response

(2.5 + Lr) x 10 x N

Te =

b

Te: Broadcast command response [s]
Lr: Maximum length of response message
N: Monitor address + 1
b: Baud rate [bits/second]