Beijer Electronics SCOM Protocol EN User Manual

Page 32

Advertising
background image

Command Reference

32

Elektronik-Systeme Lauer, MAEN976

Response Message (Acknowledge)

Maximum Lr for this Command
14

Example 1
Set the contrast level of monitor at address 0.7 (group 0, address 7) to 150 (the hexa-
decimal value of 150 is 0x96, which is represented in ASCII as “96” and split into
two ASCII codes as 0x35 0x41):

Monitor at address 0.7 (group 0, address 7) has acknowledged the new contrast level
100 (0x64):

Example 2
Query the current contrast level of monitor at address 0.7 (group 0, address 7):

Monitor at address 0.7 (group 0, address 7) has returned the current contrast level
197 (0xC5):

0

1

2

3

4

5

6

7...7+[LEN]-1

7+[LEN]

0x06 ADR

0x4D 0x43 0x43 LEN

ICHKH 0x82 Ext Param Ret

ICHKD

Ret

Value:

“00”: low … “FF”: high

Type:

Two-digit ASCII-encoded hexadecimal number

Length:

2

Description: Current contrast value

0

1

2

3

4

5

6

7...10

11

0x07

0x07

0x4D 0x43

0x43

0x04

0x1A 0x82

0x41

0x39

0x36

0xCD

0

1

2

3

4

5

6

7...12

13

0x06 0x07 0x4D 0x43 0x43 0x06 0x19 0x82 0x41 0x39 0x36 0x39 0x36 0x5E

0

1

2

3

4

5

6

7...9

10

0x07

0x07

0x4D

0x43

0x43

0x03

0x1B

0x82

0x41

0x3F

0xFD

0

1

2

3

4

5

6

7...11

12

0x06 0x07 0x4D 0x43 0x43 0x05 0x1A 0x82 0x41 0x3F 0x43 0x35 0x85