ADC EMU-830 User Manual

Page 28

Advertising
background image

Chapter 2: Installation

September 25, 2006

2-6

LTPE-UM-3159-02

Step

Action

1

Connect a serial cable from the DB-9 or DB-25 serial port on the maintenance terminal or PC to the
V.24 (RS-232) console port on the EMU front panel (

Figure 2-6

).

Figure 2-6. Connecting a Maintenance Terminal or PC to the EMU-830 Console Port

2

Configure the maintenance terminal (or PC) for the following communication settings:

• 1200 to 19200 baud (19200 baud is recommended)
• No parity
• 8 data bits
• 1 stop bit
• Flow Control to None
• VT100 Emulation, or ANSI if VT100 is not available
• If your terminal supports a modem initialization string, it should be cleared

Note:

If using a PC with the Microsoft Windows terminal emulation program, you must deselect both the

Show Scroll Bars option and the Use Function, Arrow, and Ctrl Keys for Windows option in the Terminal
Preferences menu (choose Settings | Terminal Preferences to access the Terminal Preferences menu).

Maintenance terminal or
PC with terminal emulation
program

DB-9 or DB-25
serial port

RS-232 cable

V.24 console port

EMU-830