Chapter 3: Provisioning

September 25, 2006

3-16

LTPE-UM-3159-02

Figure 3-9. LOS*, PFO* and LOSW* Alarm Reporting Screen

Shelf Alarms Menu

In the Config menu, press H to display the Shelf Alarms menu (

Figure 3-10

). This menu allows you to enable,

disable, and set the severity of the loss of shelf power, HDSL/G.SHDSL lines down, and loss of external clock alarm.

The Config menu also allows you to configure how each of the alarm relays respond to an ACO (Alarm Cut-Off). The
ACO can be activated from the EMU-830 front panel pushbutton or by connecting to ground the EXT (external) ACO
pin on the EMS-83x shelf's alarm connector. Selecting Enable (ENA) causes the associated alarm relay to be retired
(common contact connected to normally closed contact) when an ACO is received.

Figure 3-10. Shelf Alarms Menu

Note:

To select the Shelf Alarms menu for a different shelf, press ESC and then Q to return to the Network

screen, select a shelf with the

Ç

and

È

arrow keys, and press L to open the Main menu screen for that

shelf. Press C and then H to display the Shelf Alarms menu for the selected shelf.