M LS-200 (Steam)

15 Hp Blower/3 Hp Drive M otor

E

LECTRIC

S

ERIVICE

S

PECIFICATIONS

(

PER DRYER

)

IMPORTANT:

208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. Fuse ratings are dual element-time delay-current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size
according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3 dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE

SIZE*

FUSING

Dual Element

Time Delay

CIRCUIT

BREAKER

60 Hz

50 Hz

208

3/4

54

---

4

80

90

230

3

48

---

4

80

90

380

3/4

---

29

10

40

60

416

3/4

---

27

10

40

60

460

3/4

25

---

10

40

60

* AWG Stranded Type Wire...for individual lengths less than 100 feet (30.48 meters).

WARNING: 208 VAC and 230 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE

WARRANTY.

IMPORTANT: The dryer must be connected to the electrical supply shown on the data label that

is affixed to the back of the dryer, at the upper right hand corner. In case of 208 VAC

or 230 VAC, the supply voltage must match the electric service specifications of the

data label exactly.

NOTE: ADC RESERVES THE RIGHT TO MAKE CHANGES IN SPECIFICATIONS AT ANY

TIME, WITHOUT NOTICE or OBLIGATION.