3. Piping/Connections

ALL components/materials must conform to National Fuel Gas Code Specifications. It is important that

gas pressure regulators meet applicable pressure requirements and that gas meters be rated for the total

amount of ALL the appliance BTU's being supplied.

The dryer is provided with a 1-1/4" F.P.T. inlet pipe connections extending out of the top of the burner

boxes. The minimum pipe size (supply line) to the dryer is 1-1/2" N.P.T. For ease of servicing, the gas supply

line to each dryer must have its own shut off valve.

The size of the main gas supply line (header) will vary depending on the distance this line travels from the gas

meter or, in the case of L.P. (liquid propane) gas, the supply tank, other gas-operated appliances on the same

supply line, etc. Specific information regarding supply line size should be determined by the gas supplier.

NOTE: Undersized gas supply piping can create a low or inconsistent pressure which will result in

erratic operation of the burner ignition system.

Consistent gas pressure is essential at ALL gas connections. It is recommended that a 1-1/4" (3.18 cm) pipe

gas loop be installed in the gas supply line serving a bank of dryers. An in-line pressure regulator must be

installed in the supply line (header) if the (natural) gas pressure exceeds 12.0 inches of water column (29.9

mb) pressure.

IMPORTANT: A water column pressure of 3.5 inches (8.7 mb) for natural gas and 10.5 inches

(26.1 mb) for L.P. dryers is required at the gas valve pressure tap of each dryer for

proper and safe operation.

A 1/8" N.P.T. plugged tap, accessible for a test gauge connection, must be installed in the main gas supply

line immediately upstream of each dryer.

IMPORTANT: Pipe joint compounds that resist the action of natural and L.P. gases must be used.

IMPORTANT: Test ALL connections for leaks by brushing on a soapy water solution (liquid

detergent works well).

WARNING: NEVER TEST FOR GAS LEAKS WITH A FLAME!!!

ALL components/materials must conform to National Fuel Gas Code Specifications ANSI Z223.1-

LATEST EDITION.

It is important that gas pressure regulators meet applicable pressure requirements, and gas meters be rated

for the total amount of ALL the appliance Btu's being supplied.

IMPORTANT: The dryer and it's individual shut-off valve must be disconnected from the gas supply

piping system during any pressure testing of that system at test pressures in excess of

1/2 psig (3.5 kPa).

NOTE: The dryer must be isolated from the gas supply piping system by closing its individual manual

shut off valve during any pressure testing of gas supply piping system at test pressures equal to

or less than 1/2 psig (3.5 kPa).