Figure 5: Changing a keypad/display menu item

Table 7: Keypad/display menu item list

Display Keypad menu item list Abr.

Description

RO

RW

1

05

Default

rA

Reset Alarm Input

Enter 1 to clear alarms (clears all inactive alarms, except filter alarm). To enable
the alarm again, enter 0.

RW

x

//

2

HC

UVC (Heat/Cool) Mode
Output

UVCM

Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg.
Heat, 9 = Fan Only

RO

x

St

UVC State Output

UVCS

Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 =
Heat, 6 = ActiveDehum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11
= Heat Mode Cant Heat, 12 = CantCool, 13 = Emerg Heat Mode Cant Heat, 14 =
Heat Mode Low Limit, 15 = Cool Mode Low Limit

RO

x

d0

Discharge Air Temp Set
point Output

DATS Display current DA temperature set point.

RO

x

d1

Discharge Air Temp
Output

DAT Display current DA temperature.

RO

x

d2

Ventilation Cooling Low
Limit set point

VCLL Adjust economizer cooling DA temperature low limit.

RW

x

54°F

(12°C)

d3

Mechanical Cooling Low
Limit set point

MCLL Adjust mechanical cooling DA temperature low limit.

RW

x

45°F

(7°C)

SL

Slave Type Configuration

Set slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave
follows master). This feature requires a network over which the master and slave
UVCs can communicate.

RW

x

0

Eo

Effective Occupancy
Output

Display current occupancy.

RO

x

o(

Occupancy Override
Input

Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting
this variable is intended only for troubleshooting. Once you are done, cycle unit
power to clear this variable and return the UVC to normal operation.

RW

x

//

2

(o

Occupied Cooling set
point

OCS Adjust occupied cooling set point.

RW

x

73.4°F
(23°C)

(S

Standby Cooling Set
point

SCS Adjust standby cooling set point.

RW

x

77°F

(25°C)

(U

Unoccupied Cooling Set
point

UCS Adjust unoccupied cooling set point.

RW

x

82.4°F
(28°C)

ko

Occupied Heating Set
point

OHS Adjust occupied heating set point.

RW

x

69.8°F
(21°C)

kS

Standby Heating Set
point

SHS Adjust standby heating set point.

RW

x

66.2°F
(19°C)

kU

Unoccupied Heating Set
point

UHS Adjust unoccupied heating set point.

RW

x

60.8°F
(16°C)

rS

Wall Sensor Type

Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F.

RW

x

0

o1

Outside Air Damper
Position Output

OADP Display OA damper position.

RO

x

o2

OAD Min Position High-
Speed Set point

OADH

Adjust OA damper minimum position with IAF at high speed. (This variable is
factory set to 5% open when the unit is ordered with optional CO

2

DCV.)

RW

x

20%

o3

OAD Min Position Med-
Speed Set point

OADM

Adjust OA damper minimum position with IAF at medium speed. (This variable is
not used when the optional CO

2

DCV is enabled. Only OADH is active as the OA

damper minimum regardless of fan speed.)

RW

x

25%

o4

OAD Min Position Low-
Speed Set point

OADL

Adjust OA damper minimum position with IAF at low speed. (This variable is not
used when the optional CO

2

DCV is enabled. Only OADH is active as the OA

damper minimum regardless of fan speed.)

RW

x

30%