Unit mode priority – American Standard UV05 User Manual

Page 23

Advertising
background image

McQuay OM 751

23

Description of Operation

Unit Mode Priority

The UVC uses the network variables and binary inputs listed in Table 10 and Table 11 to
determine the current unit mode. Special purpose UVC unit modes have higher priority than
the normal UVC unit modes as shown in the tables.

Each table lists the highest priority items on the left to the lower priority items to the right. The
right-most columns indicate unit operation as a result of the left-most columns. The term
“Don’t care” in these tables implies that another network variable or binary input to the left
has a higher priority.

Table 10: Special purpose UVC unit mode priority

Table 11: Normal UVC mode priority

Priority result

Emergency override

input

1

Remote shutdown

binary input

Energy hold

off input

1

Energy hold

off output

2

Unit mode

output

2

Actual UVC action

Normal

3

De-energized

4

Normal

Normal

See the normal

UVC mode priority (Table 11)

Energy hold off

Energy hold off

Off

Off

Energized

5

Don’t care

Energy hold off

Off

Off

Pressurize

Don’t care

Don’t care

Don’t care

Off

Pressurize

De-pressurize

Don’t care

Don’t care

Don’t care

Off

De-pressurize

Purge

Don’t care

Don’t care

Don’t care

Off

Purge

Shutdown

Don’t care

Don’t care

Don’t care

Off

Off

1. Network input.
2. Network output.
3. Normal indicates the UVC power-up condition.
4. De-energized indicates that the contacts connected to this binary input are open.
5. Energized indicates that the contacts connected to this binary input are closed.

Priority result

Application override

input

1

1. Network input.

Unit mode override

input

1

Unit mode output

2

2. Network output.

Normal (Auto)

3

3. Normal (Auto) is the normal UVC power-up state.

Normal (Auto)

3

Heat
Cool

Emergency heat

Heat

Heat

Cool

Cool

Night purge

Night purge

Off

Off

Emergency heat

Emergency heat

Fan only

Fan only

Heat

Don’t care

Heat

Cool

Don’t care

Cool

Night purge

Don’t care

Night purge

Off

Don’t care

Off

Emergency heat

Don’t care

Emergency heat

Fan only

Don’t care

Fan only