The UVC is been provided with a number of configuration variables as listed in the following
table. These configuration variables are stored in UVC non-volatile memory. For a description
of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED
15065.

Table 26: UVC configuration parameters (OM 751)

Configuration Parameter Name

Abr.

Notes

Default

LUI Menu

Item

1

Occupied Cooling Setpoint

OCS

73°F (23°C)

Co

Standby Cooling Setpoint

SCS

77°F (25°C)

C5

Unoccupied Cooling Setpoint

UCS

82°F (28°C)

CU

Occupied Heating Setpoint

OHS

70°F (21°C)

Ho

Standby Heating Setpoint

SHS

66°F (19°C)

H5

Unoccupied Heating Setpoint

UHS

61°F (16°C)

HU

Local Bypass Time

Tenant override

120 min

Space CO

2

Setpoint

2

CO

2

S

1200 PPM

Space Humidity Setpoint

2

RHS

used with both active (reheat) and passive dehumidification
sequences

60% Rh

Emergency Heat Enable

0 = disable, 1 = enable (uses auxiliary heat where primary heat is
not applicable)

1

H1

Emergency Heat Setpoint

EHS

54°F (12°C)

H2

Emergency Heat Shutdown
Configuration

0 = no emergency heat during shutdown, 1 = emergency heat
available during shutdown

0

H3

Wall Sensor Type

2

0 = +/- 3°F, 1 = 55°F to 85°F

0

r5

Slave Type Configuration

2

0 = independent slave, 1 = dependent slave

0

SL

OAD Min Position High-Speed Setpoint

OADH

(this variable will be factory set to 5% open when the unit is ordered
with optional CO

2

DCV)

20% open

o2

OAD Min Position Med-Speed Setpoint

OADM

(this variable is ignored when the unit is ordered with optional CO

2

DCV)

25% open

o3

OAD Min Position Low-Speed Setpoint

OADL

(this variable is ignored when the unit is ordered with optional CO

2

DCV)

30% open

o4

Exhaust Interlock OAD Min Position
Setpoint

EOAD

OA damper minimum position when the exhaust interlock input is
energized

99% open

o5

Energize Exhaust Fan OAD Setpoint

OADE defines position above which exhaust fan output will be energized

12% open

o6

OAD Max Position Setpoint

OAMX

99% open

o7

OAD Lockout Enable

0 = disable, 1 = enable (this variable will be factory set to 1 when
the unit is ordered as a recirc unit with no OAD)

0

o8

OAD Lockout Setpoint

OALS

OA temperature below which the OA damper will remain closed
(this variable will be factory set to –99°C when the unit is ordered
as a recirc unit with no OAD)

36°F (2°C)

o9

Economizer Enable

0 = disable, 1 = enable

1

E1

Economizer OA Temp Setpoint

ETS

68°F (20°C)

E2

Economizer IA/OA Temp Differential

ETD

2°F (1°C)

e3

Economizer OA Enthalpy Setpoint

EES

25 btu/lb (58 kJ/kg)

e5

Economizer IA/OA Enthalpy Differential

EED

1.3 btu/lb (3 kJ/kg)

e6

External BI-3 Configuration

0 = Ventilation Lockout, 1 = Exhaust Interlock

0

B3

External BO-3 Configuration

0 = Exhaust Fan On/Off, 1 = Auxiliary Heat

0

B6

Filter Alarm Enable

0 = disable, 1 = enable

0

CE

Filter Change Hours Setpoint

fan run hours between filter change alarms

700 hrs