McQuay OM 751

Description of Operation

Figure 16: Effective set point calculations

Table 15: Set point calculation examples

Examp

le A

Given
OccupancyMode = Occupied or BypassHeat/CoolMode = Heat
SpaceTempSetpoint = (not used)
SetpointOffset = (not used) = 0.0°F
SetpointShift = (not used) = 0.0°F
OHS = 69.8°F
Effective set point calculations
EffectiveSetpoint = OHS + SetpointOffset + SetpointShift = 69.8 + 0.0 + 0.0 = 69.8°F

E

x

amp

le B

Given
OccupancyMode = Occupied or BypassHeat/CoolMode = Heat
SpaceTempSetpoint = 71.0°F
SetpointOffset = -1.0°F (occupant adjustment on remote wall sensor, or LUI)
SetpointShift = (not used) = 0.0°F
OCS = 73.4°F, OHS = 69.8F
Effective set point calculations
AbsoluteOffset = (OCS – OHS) / 2 =(73.4°F – 69.8°F) / 2 = 1.8°F
EffectiveSetpoint = SpaceTempSetpoint – AbsoluteOffset + SetpointOffset + SetpointShift = 71.0 -
1.0 - 1.0 + 0.0 = 68.2°F

Set Point

Offset Input

(network input)

WallSensorType

Config. Value

1

+3°F/–3°F

Wall Sensor

Network Value

Space Temp

Set Point Input

(network input)

0

55°F/85°F

Wall Sensor

Network Value

Set Point

SetptOffset

Occupied Cooling Set Point (OCS)

Standby Cooling Set Point (SCS)

Unoccupied Cooling Set Point (UCS)

Occupied Heating Set Point (OHS)

Standby Heating Set Point (SHS)

Unoccupied Heating Set Point (UHS)

Occupied Cooling Set Point Shift (OCSS)

Standby Cooling Set Point Shift (SCSS)

Unoccupied Cooling Set Point Shift (UCSS)

Occupied Heating Set Point Shift (OCSS)

Standby Heating Set Point Shift (SHSS)

Unoccupied Heating Set Point Shift (UHSS)

SetptShift (network inputs)

Occupancy Temperature Setpoints
(network configuration variables)

Local User

Interface

+5°F/–5°F

AbsOffsetOccupied = Setpoint - (OCS + OHS)/2
AbsOffsetStandby = Setpoint - (SCS + SHS)/2

Occupied and Bypass Modes
EffectiveCoolSetpoint = OCS + AbsOffsetOccupied + SetptOffset + OCSS
EffectiveHeatSetpoint = OHS + AbsOffsetOccupied + SetptOffset + OHSS

Standby Mode
EffectiveCoolSetpoint = SCS + AbsOffsetStandby + SetptOffset + SCSS
EffectiveHeatSetpoint = SHS + AbsOffsetStandby + SetptOffset + SHSS

Unoccupied Mode
EffectiveCoolSetpoint = UCS + UCSS
EffectiveHeatSetpoint = UHS + UHSS

If both entering paths have
valid values, then the network
value has priority.

Effective Set Point Calculations for each Occupancy Mode

If both entering paths have
valid values, then the keypad/display value
has priority.