Networked space humidity sensor capability, Networked outdoor humidity sensor capability, Co2 demand controlled ventilation (optional) – American Standard UV05 User Manual

Page 34: Networked space co2 sensor capability, Networked space co, See “co2 demand controlled, E (see “co2 demand, Demand controlled ventilation (optional), Sensor capability

Advertising
background image

34

McQuay OM 751

Description of Operation

Networked Space Humidity Sensor Capability

A networked space humidity sensor can be network interfaced with the Space Humidity Input
variable. When the Space Humidity Input variable is used (valid value), it automatically
overrides the hard-wired space humidity sensor (if present).

Networked Outdoor Humidity Sensor Capability

A networked outdoor humidity sensor can be network interfaced with the Outdoor Humidity
Input variable. When the Outdoor Humidity Input variable is used (valid value), it
automatically overrides the hard-wired outdoor humidity sensor (if present).

CO

2

Demand Controlled Ventilation (optional)

Ventilation equipment typically uses fixed damper positions to determine the amount of OA
for proper ventilation within the space. Most commonly, the fixed position of the OA damper
is based on the maximum number of occupants the space is designed to accommodate.
However, this fixed OA damper operation ignores the fact that most spaces during the day
have varying occupancy levels and may only rarely reach maximum design occupancy levels.
This type of fixed damper control for ventilation is energy wasteful since you are treating OA
not actually needed for ventilation during low occupancy levels.

People produce CO

2

when they breath; the CO

2

level within the space has a direct relationship

with the number of people within that space.

The UVC can optionally be factory configured to provide CO

2

-based Demand Controlled

Ventilation (DCV). The CO

2

DCV function is useful in saving the energy typically wasted in

treating OA not actually needed for ventilation within a space during occupancy levels below
maximum design. The CO

2

DCV function uses a PI-loop control to adjust the OA damper

above the minimum position as needed to maintain the Space CO

2

Setpoint (1200 PPM

default).

The minimum damper position used with CO

2

DCV typically can be set at ~20% of the

minimum position that would be used without CO

2

DCV. For example, if the minimum OA

damper position typically is 20% then when using CO

2

DCV, you could set the new minimum

OA damper position as low as 4% (e.g., 20% × 0.20 = 4%). This new, smaller minimum OA
damper position then should provide enough ventilation to keep odors in check within the
space for most applications.

Note – The

CO

2

DCV function can increase the OA damper position past that required by the

economizer and vice versa.

If odors within the space become a problem, increase the OA damper minimum position

as needed to eliminate these odors. It may be necessary with new construction or after
renovation to raise the minimum position for some time period to help reduce odor build-
up due to the out-gassing of new construction material and then return the minimum OA
damper position at a later date.

If the CO

2

Demand Controlled Ventilation (DCV) option is used, the UVC only uses the IA

fan high speed OA damper minimum position regardless of fan speed. The DCV function
adjusts the OA damper above this minimum as needed. In this case, the IA fan high speed
OA damper minimum position is factory set at 5%.

Networked Space CO

2

Sensor Capability

A networked space CO

2

sensor can be network interfaced with the Space CO

2

Input variable.

When the Space CO

2

Input variable is used (valid value), it automatically overrides the hard-

wired space CO

2

sensor (if present).