American Standard UV05 User Manual

Page 48

Advertising
background image

48

McQuay OM 751

UVC Configuration Parameters

Primary Cool Proportional Band

18°F (10°C)

Primary Cool Integral Time

180 sec

Secondary Cool Proportional Band

18°F (10°C)

Secondary Cool Integral Time

600 sec

Discharge Air Temp Proportional Band

4°F (2.22°C)

Discharge Air Temp Integral Time

300 sec

CO

2

Proportional Band

2

100 PPM

CO

2

Integral Time

2

600 sec

Ventilation Cooling Low Limit Setpoint

VCLL discharge air low limit during ventilation or economizer cooling

54°F (12°C)

d2

Mechanical Cooling Low Limit Setpoint MCLL discharge air low limit during mechanical (compressor) cooling

45°F (7°C)

d3

Discharge Air High Limit

DAHL

140°F (60°C)

Space Fan Off Delay

30 sec

Fan Cycling Configuration

space fan operation during occupied, standby and bypass
occupancy modes: 2 = continuous, 3 = cycle

2

CF

Space Fan Speed Changes Per Hour

example: 6/60min = 10min (maximum of 1 fan speed change every
10min when fan in auto)

6

Space Fan Run Time Reset

reset total run time: 1 = reset (you must return the variable back to
0 after reset)

0

Compressor Run Time Reset

reset total run time: 1 = reset (you must return the variable back to
0 after reset)

0

Compressor Enable

0 = disable, 1 = enable

1

C!

Compressor Minimum On Time

180 sec

Compressor Minimum Off Time

300 sec

Compressor Cooling Lockout Setpoint CCLO OA temperature below which compressor cooling is not allowed

63.5°F (17.5°C)

Compressor Envelope Cool Max In

120°F (48.89°C)

Compressor Envelope Cool Min In

28°F (-2.22°C)

Compressor Envelope Cool Max Out

160°F (71.11°C)

Compressor Envelope Cool Min Out

40°F (4.44°C)

Compressor Envelope Cool Max Ratio

0.00

Compressor Envelope Cool Max Offset

88°F (48.89°C)

Compressor Envelope Cool Min Ratio

0.0

Compressor Envelope Cool Min Offset

-4°F (-2.22°C)

Auxiliary Heat Start Differential

AHSD degrees above auxiliary heat start point where auxiliary heat ends

2°F (1°C)

A1

Auxiliary Heat End Differential

AHED degrees above auxiliary heat start point where auxiliary heat ends

2°F (1°C)

A2

Auxiliary Heat Configuration

0 = normally open heat device (hot water valve, etc.),
1 = normally closed heat device (electric heat, etc.)

0

A3

Space Humidity Sensor Enable

2

0 = disable, 1 = enable (this variable will be factory set to 1 when
the unit is ordered with optional humidity sensor)

0

Outdoor Humidity Sensor Enable

2

0 = disable, 1 = enable (this variable will be factory set to 1 when
the unit is ordered with optional humidity sensor)

0

Configuration Parameter Name

Abr.

Notes

Default

LUI Menu