Troubleshooting humidity sensors – American Standard UV05 User Manual

Page 45

Advertising
background image

McQuay OM 751

45

Diagnostics and Service

3

Use the temperature reading from Step 2 to determine the expected sensor resistance from
Table 23.

4

Using a calibrated ohmmeter, measure the actual resistance across the two sensor leads.

5

Compare the expected resistance to the actual resistance.

6

If the actual resistance value deviates substantially (more than 10%) from the expected
resistance, replace the sensor.

Table 23: Temperature versus resistance

Troubleshooting Humidity Sensors

The UVC is configured to use a 0–100% RH, 0–5 VDC, capacitive humidity sensor. Each
sensor is calibrated according to the table shown.

Use the following procedure to troubleshoot a suspect sensor:

1

Disconnect the sensors output voltage lead from the UVC analog input.

2

Using some other calibrated humidity sensing device, take a humidity reading at the sensor

location.

3

Use the humidity reading from Step 2 determine the expected sensor voltage from
Table 24.

4

Using a calibrated multi-meter, measure the actual voltage across the yellow and white
sensor leads.
Wire color definitions:
White = ground
Yellow = output VDC
Blue = supply VDC

5

Compare the expected voltage to the actual voltage.

6

If the actual voltage value deviates substantially (more than 10%) from the expected
voltage, replace the sensor.

°F (°C)

Resistance in ohms

°F (°C)

Resistance in ohms

–40 (–40)

613

113 (45)

1195

–31 (–35)

640

122 (50)

1237

–22 (–30)

668

131 (55)

1279

–13 (–25)

697

140 (60)

1323

–4 (–20)

727

149 (65)

1368

5 (–15)

758

158 (70)

1413

14 (–10)

789

167 (75)

1459

23 (–5)

822

176 (80)

1506

32 (0)

855

185 (85)

1554

41 (5)

889

194 (90)

1602

50 (10)

924

203 (95)

1652

59 (15)

960

212 (100)

1702

68 (20)

997

221 (105)

1753

77 (25)

1035

230 (110)

1804

86 (30)

1074

239 (115)

1856

95 (35)

1113

248 (120)

1908

104 (40)

1153

CAUTION

The humidity sensor is not protected against reversed polarity.
Check carefully when connecting the device or damage can
result.