Description of Operation

Expanded (optional)—Temperature Comparison with OA Enthalpy Setpoint Economizer

(Strategy 1)

Leading Edge (optional)—Temperature Comparison with Enthalpy Comparison Economizer

(Strategy 2)

Temperature Comparison Economizer (default)

If the default Basic economizer function is selected, the unit ventilator is provided from the
factory without the optional IA and OA humidity sensors. In this case, the UVC is factory set
for Economizer Strategy 1—the UVC automatically detects that no OA humidity sensor is
present and adjusts to use the Temperature Comparison Economizer function.

Temperature Comparison with OA Enthalpy Setpoint Economizer (optional)

If the optional Expanded economizer function is selected, the unit ventilator is provided from
the factory with the optional OA humidity sensor, which is used along with the OA
temperature sensor to calculate OA enthalpy. In this case, the UVC is factory set for
Economizer Strategy 1 and uses the Temperature Comparison with OA Enthalpy Setpoint
Economizer function.

Note – Temperature Comparison with OA Enthalpy Setpoint Economizer requires an optional OA

humidity sensor.

Temperature Comparison with Enthalpy Comparison Economizer (optional)

If the optional Leading Edge economizer function is selected, the unit ventilator is provided
from the factory with both the IA humidity and OA humidity sensors, which are used along
with the IA temperature and OA temperature sensors to calculate IA enthalpy and OA
enthalpy. In this case, the UVC is factory set for Economizer Strategy 2 and uses the
Temperature Comparison with Enthalpy Comparison Economizer function.

Note – Temperature Comparison with Enthalpy Comparison requires both an optional OA

humidity sensor and an optional IA humidity sensor.

Table 18: Economizer enable/disable tests defined

Table 19: How economizer enable/disable tests are selected

Note: The hard-wired sensor and the equivalent input must both be unreliable for the value to be considered

unreliable.

Tests

Economizer
enable/disable tests

Enable test

Disable test

A

OA temp set point

EffectiveOATemp < (EconOATempSetpt – EconTempDiff)

EffectiveOATemp >= EconOATempSetpt

B

IA/OA differential temp EffectiveOATemp < (EffectiveSpaceTemp – 3.6°F – EconTempDiff) EffectiveOATemp >= (EffectiveSpaceTemp – 3.6°F)

C

OA enthalpy set point

EffectiveOAEnthalpy < (EconOAEnthalpySetpt –

EconEnthalpyDiff)

EffectiveOAEnthalpy >= EconOAEnthalpySetpt

D

IA/OA differential

enthalpy

EffectiveOAEnthalpy < (EffectiveSpaceEnthalpy –

EconEnthalpyDiff)

EffectiveOAEnthalpy >= EffectiveSpaceEnthalpy

Economizer

strategy

Space temp sensor

OA temp sensor

Space humidity

sensor

OA humidity sensor

Economizer enable/

disable tests

All

Unreliable

Don’t care

Don’t care

Don’t care

OA damper closed

Don’t care

Unreliable

Don’t care

Don’t care

OA damper closed

Basic

Reliable

Reliable

Don’t care

Unreliable

Test B

Reliable

Reliable

Don’t care

Reliable

Test C

Expanded

Reliable

Reliable

Don’t care

Reliable

Test C and Either

Test B or Test A

Leading Edge

Reliable

Reliable

Reliable

Reliable

Test D and Test B

Reliable

Reliable

Unreliable

Reliable

Test B

Reliable

Reliable

Reliable

Unreliable

Test B

Reliable

Reliable

Unreliable

Unreliable

Test B