McQuay OM 751

19

Description of Operation

Figure 12: Cool mode super state diagram

Econ State (State 3)

The Econ state is a “normal” state during Cool mode. The Econ state typically is active in the
Cool mode when primary cooling (economizer) is available and adequate to meet the cooling
requirements.

When the Econ state becomes active, the UVC uses economizer cooling (see “Economizer
Operation” on page 32) as
needed to maintain the effective cooling set point (see “Space
Temperature Set Points” on page 26).
If cooling is not required while in the Econ state, the
UVC can “idle” in the Econ state until cooling is required or until there is a call to switch to
another mode or state.

The UVC monitors the DAT to ensure it does not fall below VCLL.

The CO

2

demand controlled ventilation function (optional) will be active (see “CO2 Demand

Controlled Ventilation (optional)” on page 34) and the OA damper is adjusted as needed to
maintain the CO

2

set point.

Econ

EconMech

Mech

3

1

2

CantCool

C

CoolMode

SuperState

DAHeat

LowLimit

4

F

LLPI=SatLow (2min)

AND

DAT>(VCLL+1.8F)

HeatPI=SatHi(2min)

AND DAT<VCLL

Space

HighCO2

AND

HeatPI=SatLow

AND

DAT>VCLL

Space=HighCO2

OR

DAT<VCLL

UVCMode

Cool AND UVCMode

Auto

OR

UVCMode=Auto AND Space=Cold AND

MechPI=SatLow(3min) AND

EconPI=SatLow

UVCMode=Cool

OR

UVCMode=Auto AND Space=Warm

Econ

Available

AND

MechCool

Available

Econ = Available

AND

MechCool

Available

Econ

Available

AND

MechCool=Available

MechPI=SatLow (3min) AND

EconMechTimer=Expired

(3 minutes) OR

MechCool

Available

Econ

Available

Econ=Available

MechCool

Available

Econ

Available

AND

MechCool=Available

Transition

Point

EconTimer=Expired

(3 minutes) AND

EconPI=SatHi AND

MechCool=Available