McQuay OM 751

49

UVC Configuration Parameters

OAD Stroke Time

90 sec

Split-System OA/DX Coil Temp

used on split-system units only to partially disable the compressor
envelope by setting the outside DX coil temperature to a fixed valid
value, enter 122°F (50°C) on split-systems, use 327.67 for self-
contained units (327.67 = invalid)

327.76

Application Name and Version Label

Compressor Start Delay

adjust the compressor delay used to prevent multiple compressor
units from starting simultaneously (each unit or group of units
should have a different delay setting)

0 sec

C6

Outdoor Fan Delay

10 sec

1. Indicates parameters accessible through the keypad/display.
2. Requires optional equipment.

Configuration Parameter Name

Abr.

Notes

Default

LUI Menu

Item